HVAC 2.0 Diaries

From Green Garage Detroit
Revision as of 14:50, 22 September 2011 by Joeg (Talk | contribs) (Sept 22 2011)

Jump to: navigation, search

Sept 22 2011


  • Solar Thermal Collectors (@ 6:20am)
    • P9 went off last night
    • Array Out = 73F
    • Tank 1 = 91F (Passed 90F!!!)
    • BTU Production
      • Weekly
        • This is 880,000 BTU's in a week.
        • This is 314 BTU/sf/day...which is on the low side.
      • Daily (Today)
        • Partially Sunny day: 7F tank rise * 4800gal * 8.33lbs/gal / 400 sf = 700 BTU/sf/day <<== planned 750BTU/sf/day
    • Air Core = 49F
  • Ventilation
    • Booster fan was on all night- this is in mode 7 which calls for dehumidification
    • ERV was off last night
    • Altherma shows On? Trying to dehumidify. unit was off do to low water pressure.
    • 10:43 AM solar panels start- air temp-58, panel air temp 120, tank temp 90.9

Sept 21 2011


  • Solar (Lunar) Thermal Collectors
    • Ran all night!!
    • Tank 1 = 84F
    • Array Out = 88F?
  • Ventilation
    • Dehumidification was on most of the day
      • It produced water in the drain line!!
      • Graphing Indoor RH showed it was slowly going down.
      • Some risk this it cant' keep up with very high humidity (91%RH today!)
  • Earth Room
    • Looks like Earth room hits 90F within 30 minutes of running
    • Issue with the exhaust fan turning on and off rapidly because it turns on at 90F and turns off at 89F.
    • Not providing value because outdoor temp is 70F and earth room gets to 90F within 30 minutes.
    • Opportunity to do some "thermal pumping" in the shoulder seasons...heating 30 mins, cooling (dehumid) 30 mins, cycles.