Difference between revisions of "Frozen Solar Panel Incident"
From Green Garage Detroit
Tom Brennan (Talk | contribs) (→1/4/12) |
(→What is the location of the failure in the panels?) |
||
Line 16: | Line 16: | ||
** It showed water leakages inside two panels....Panels #5? and #10. | ** It showed water leakages inside two panels....Panels #5? and #10. | ||
** Please place picture gallery here. | ** Please place picture gallery here. | ||
+ | |||
+ | ==== What is the sequence for the panel heating?==== | ||
+ | *Valves and pumps involved in solar heating: Valve 1, Valve 2, Valve 4 and Pump 9 | ||
+ | **Default position | ||
+ | ***Valve 1 | ||
+ | ***Valve 2 | ||
+ | ***Valve 4 | ||
+ | ***Pump 9 | ||
+ | |||
+ | |||
+ | |||
==== What is the location of the failure in the panels? ==== | ==== What is the location of the failure in the panels? ==== |
Revision as of 15:03, 4 January 2012
Contents
What We Know
- Date: 1/3/2011
- Time: Approximately 10:30am situation was detected
- Found using the Green Garage HVAC website
- Solar Panel Air Temp = 195F (sure)
- T-out for the panels = 64F <needs to be confirmed...very close to correct
- Pump 9 = On
- Tank Temp = 97F <needs to be confirmed...very close to correct
- The evidence indicated that the panels were very hot but no water was running through the panels as T-out was in the 60's (not it's normal 110F).
- Ambient weather
- Outdoor temp was 18F
- Sunny with intermittent clouds
- Wind was moderate (10 mph range) with gusts <needs to be confirmed
- Wind chill that morning was -2F (from Tom who road his bike!)
- Joe G. took pictures of the panels at about XX:XXpm (< please advise)
- It showed water leakages inside two panels....Panels #5? and #10.
- Please place picture gallery here.
What is the sequence for the panel heating?
- Valves and pumps involved in solar heating: Valve 1, Valve 2, Valve 4 and Pump 9
- Default position
- Valve 1
- Valve 2
- Valve 4
- Pump 9
- Default position
What is the location of the failure in the panels?
- Appears to be a fracture in the copper tubing in the thermal transfer body (under the glass) of the panel.
- Need to confirm location of the failure occurred in the panel system.
- Key Questions
- Where is the failure location in panels #5 and #10
- Are they the same?
- Does it look like a burst tubing?
- What is the current state of the panels? Frozen water in them? Are they drained?
When did the failure occur?
- Option 1 - It occurred on 1/3/2011
- Option 2 - The leak has been occurring for some time
- Key Questions
- When was the last time the panels ran before 1/3/2011?
- What is the tank level? If it's been leaking for a while, the tanks would be low.
- Any evidence of routine leaking up on the roof? Water...deposits showing steam of water?
What caused the panel failure?
- Potential reason for the leakages:
- Potential Cause #1 - Panel manufacturing failure
- Not likely since the panels had been running without leakages (need to be confirmed)
- Two panels failed in the same spot at the same time
- Panels were never tested for water flow before installation.
- Potential Cause #2 - Water froze in the copper tubes causing them to burst
- Note that the leaks in the two panels were at the same level above the bottom of the panel.
- Note that the these were two panels later in the series...water is cooler.
- Potential Cause #1 - Panel manufacturing failure
- Key Questions
- What is the best way to determine the cause of the failure? Wait for warm weather and run water through the system. Currently looks like Friday is a good day.
- What does Alan Rushforth have to say about this?
- What is the temperature of the pipe / tube at the bottom of the panel that fills first?
Why did the cause of the failure occur?
- IF it was caused by frozen pipes (pure conjecture at this point 1/4/12), why did they freeze?
- Potential Reason #1 - The water froze because the panels were too cold on the initial filling
- What temperature was the panel air at the time of filling?
- Could the water at 97F(Tank Temp) lose enough heat as it was going through the system to freeze?
- Could all the panels not be the same temp at the time of filling?
- Could the temp gauge at the top of the panels be inaccurate?
- Could there be a big difference in the temp at the top of the panel and the temp at the bottom of the panel?
- Could the programming have an error in it and pump #9 came on too early or incorrectly?
- Potential Reason #2 - Panels didn't drain properly this time or Panels never drained properly
- Could design of drainback have a flaw i.e. the panels don't fully drain.?
- If the leaks are actually 2/3 up the panel this seems unlikely.
- We have had colder nights and we didn't have a problem...freezing
- Could valve #? for drainback not open correctly the last time the panels needed to drain?
- Could the water in the panels have frozen before it fully drained?
- Could design of drainback have a flaw i.e. the panels don't fully drain.?
- Potential Reason #1 - The water froze because the panels were too cold on the initial filling
How do we recover?
- Option #1 - Repair the panels
- Manufacturer says that this would be difficult...they are no help
- Option #2 - Replace the panels
- Could do this first and then repair panels (Option #1) later.
- Would need to make sure that cause is accurately determined and corrected.
- Could only run panels when outside temp is above 20F (plus low winds)
- Option #3 - Wait until spring (consistently warmer weather)
- Better for testing and working out all possible issues
- Option # 4 - Reconfigure from 10 panels to 8 panels.
- Costly in labor and then need to change back.
Next Steps
1/4/12
- Check on availability of replacement panels and mounting materials (Joe)
- Get input from others...email, phone (Joe, Tom)
- Complete recording of what "we know" section on wiki
- Research using data from Niagara System
- Answer ... When did the failure occur?
- Plan test for Friday with Labs