==== Goals of Lab ====
+
==== Goals of Experiment ====
 
* Determine if we met our air leakage design criteria of 0.1 AC/hr leakage rate.
 
* Determine if we met our air leakage design criteria of 0.1 AC/hr leakage rate.
 
* Verify general effectiveness of sealing of building envelope with construction now complete.
 
* Verify general effectiveness of sealing of building envelope with construction now complete.
 
* Measure potential energy and comfort impact of a window being left cracked open to try to inform occupants.
 
* Measure potential energy and comfort impact of a window being left cracked open to try to inform occupants.
  
==== Decisions to be made from Lab ====
+
==== Decisions to be made from Experiment ====
 
* Determine if any additional sealing  or gasketing is required.
 
* Determine if any additional sealing  or gasketing is required.
  
Line 55: Line 56:
  
 
==== Participants ====
 
==== Participants ====
* Byczinski, Kenco - Perform test
+
* Ken Byczinski, Kenco - Perform test
* Catey - Labs POC
+
* Laurie Catey - Labs POC
 
* Library (USL) - assist with media (Flip, camera)
 
* Library (USL) - assist with media (Flip, camera)
 
* Interested participants:
 
* Interested participants:
** Helen - photos, etc.
+
** Peggy Brennan - videographer, photos
** Peggy - videographer
+
** Kirsten Lyons - assist, record data (not on Wednesday)
** Kirsten - assist, record data (not on Wednesday)
+
** Michael Paciero - remote interface
** Michael Paciero
+
  
 
==== Collaboration ====
 
==== Collaboration ====
Line 85: Line 85:
 
=== References ===
 
=== References ===
 
----
 
----
 
+
* [https://docs.google.com/spreadsheet/ccc?key=0AtbEzr-Y2qtadFpvQ2FNcmlJNkJid18taFVYRkNDMlE&authkey=CO2rm5MB&hl=en_US&authkey=CO2rm5MB Blower Door Test Workbook]
 
* [https://docs.google.com/spreadsheet/ccc?key=0AtbEzr-Y2qtadEpfLWZTUTNENkMyVTNGYUN2aGFZLVE&hl=en_US Experiment Tracker] - summary of all experiments & experiment project management
 
* [https://docs.google.com/spreadsheet/ccc?key=0AtbEzr-Y2qtadEpfLWZTUTNENkMyVTNGYUN2aGFZLVE&hl=en_US Experiment Tracker] - summary of all experiments & experiment project management
* [https://docs.google.com/spreadsheet/ccc?key=0AtbEzr-Y2qtadDJVaDI3LS1BX1JiRDUtem91cWhyeWc&hl=en_US Experiment Template] - report template for actual conducting of experiment
 
  
 
=== Questions ===
 
=== Questions ===
* Is there other test equipment that might handle the size of our building? Could multiple test apparatus achieve our pressure difference?
+
* Is there other test equipment that might handle the size of our building? (Centrifugal fan or using our equipment)
 +
* Could multiple test apparatus achieve our pressure difference? (Yes; Ken will bring two sets of test equipment with him)
  
 
=== TO DO ===
 
=== TO DO ===
* Plan / Do / Check / Act / Repeat
+
* ''Plan / Do / Study / Act / Repeat''
 
* Research blower door testing online to find if any other conditions/process requirements.
 
* Research blower door testing online to find if any other conditions/process requirements.
** [[http://nachi.org/blower-door-text.htm Blower Door Info]] - temperature, barometric pressure affect test - correction factor
+
** [http://www.infiltec.com/inf-btst.htm Outline of Blower Door Test]]
* Calculate the CFM for Annex and Historic Bldg corresponding to 0.1 AC/hr.
+
** [http://www.bpi.org/Web%20Download/BPI%20Standards/Building%20Analyst%20Professional_2-28-05nNC-newCO.pdf BPI Calculations & Factors]
* Get small scale floor plans to note results and observations.
+
** [http://en.wikipedia.org/wiki/Blower_door Blower Door Basics]
* Review experiment process - group, Ken
+
** [http://www.nachi.org/blower-door-test.htm Blower Door Info] - temperature, barometric pressure affect test - correction factor
* Confirm October 6, 2011 12-2 p.m. okay with Ken
+
* Calculate the CFM for Annex and Historic Bldg corresponding to 0.1 AC/hr - Kirsten
 +
* Get small scale floor plans to note results and observations - Kirsten
 +
* Review experiment process - group, Ken - DONE
 +
* Confirm October 6, 2011 12-2 p.m. okay with Ken - CONFIRMED. DONE
  
  

Latest revision as of 15:14, 7 November 2011

Initial Blower Door Test.JPG

return to Sustainability Labs
return to Labs Highlights

return to Current Labs Summary

Blower Door Test Experiment


Goals of Experiment

  • Determine if we met our air leakage design criteria of 0.1 AC/hr leakage rate.
  • Verify general effectiveness of sealing of building envelope with construction now complete.
  • Measure potential energy and comfort impact of a window being left cracked open to try to inform occupants.

Decisions to be made from Experiment

  • Determine if any additional sealing or gasketing is required.

Expected Outcomes

  • Determine a value for our overall building leakage (or at least observe leakage with smoke tracer if unable to measure).
  • Provide educational information to building occupants on the effects of leaving windows open.

Methodology


General

  • No occupants opening/closing doors/windows in building (SEND OUT NOTICE AHEAD OF TIME FOR TEST).
  • Seal up any openings between Annex and Historic Building (CHECK WITH KEN; Kirsten has visquine).
    • Seal up damper openings in exterior wall with visquine because pressure measurement so low.
    • Seal openings for conduits/wires/pipes in wall between Annex and Historic.
    • Seal ductwork openings between Annex and Historic.
  • Make sure basement is segregated from rest of building; area is excluded from test.
  • Start out sealing gaps in doors and windows. Incrementally test envelope construction, door/window gaps, then open window to observe impact.
  • Prefer to perform test on low/no wind day (CHECK WEATHER).
  • Building air systems off initially and sealed closed at outside envelope.
  • Consider putting differential pressure meters in multiple locations (use blower door test apparatus meter, digital micro-manometer, magnehelic gauge). Calibrate meters together first to check for differences.
  • Use building exhaust system as alternate approach if pressure differential from testing apparatus inadequate.

Process Measurements

  • Record outside conditions; temp/RH/barometric pressure/wind speed & direction/weather conditions
  • Record inside conditions; temp/RH
  • Building pressure differential (Kenco equipment; LL Catey meters).
  • Building leakage pressure (Kenco equipment then convert to CFM; otherwise bldg. equip CFM with smoke tracer).
  • Use smoke tracer to check for leakage locations.
  • Velocity/CFM through slightly open window with building under 0.02" w.c. negative

Resources Required

  • Equipment for Test
    • Blower Door Test Apparatus - Kenco
    • TSI Digital Micro-Manometer - LL Catey
    • Magnehelic Gauge - LL Catey
    • Green Garage DDC Online through Laptop - LL Catey
  • Media to Document
    • Measurement recording: test form (LLC check with KEN or create in Experiment Workbook)
    • Video - Flip camera USL
    • Photos - Canon camera USL

Participants

  • Ken Byczinski, Kenco - Perform test
  • Laurie Catey - Labs POC
  • Library (USL) - assist with media (Flip, camera)
  • Interested participants:
    • Peggy Brennan - videographer, photos
    • Kirsten Lyons - assist, record data (not on Wednesday)
    • Michael Paciero - remote interface

Collaboration

  • USL - media
  • Kenco - conducting testing, equipment
  • LL Catey Engineering Services - equipment

Help Wanted

  • Open to observers

Scheduling & Sequencing

  • Sequencing/Prerequisites
    • No occupants opening/closing doors or windows during test.
    • Ventilation systems must be balanced.
    • Must have control of ventilation systems.
    • Openings/gaps sealed ahead of time.
  • Scheduling
    • Experiment design - 9/23/2011 - REVIEW
    • Conduct field testing - 10/6/2011 between 12 p.m. - 2 p.m. (prep starting at 11:30 a.m.)

References


Questions

  • Is there other test equipment that might handle the size of our building? (Centrifugal fan or using our equipment)
  • Could multiple test apparatus achieve our pressure difference? (Yes; Ken will bring two sets of test equipment with him)

TO DO

  • Plan / Do / Study / Act / Repeat
  • Research blower door testing online to find if any other conditions/process requirements.
  • Calculate the CFM for Annex and Historic Bldg corresponding to 0.1 AC/hr - Kirsten
  • Get small scale floor plans to note results and observations - Kirsten
  • Review experiment process - group, Ken - DONE
  • Confirm October 6, 2011 12-2 p.m. okay with Ken - CONFIRMED. DONE